Can a Greenstar Oil boiler be used with the existing conventional flue?
The conventional flue must comply with the following:
- Open (conventional) flued appliances must not be installed in or take ventilation from a bedroom, bathroom or bedsitting room
- The flue system must be in accordance with BS5410: Part 1 and the current Building Regulations
- The flue must be constructed of materials suitable for the use of condensing combustion products
- External flue systems must be of insulated type
- Brick and masonry chimneys must be lined with a suitable non-combustible material and properly jointed to withstand the effects of the working temperature (minimum rating of material 120°C) of the appliance and any condensate which may be produced
- All flue joints must be sealed to prevent the leakage of condensate and combustion products
- Ensure that joints are made so that the condensate runs away and is not collected within the joint NOTE: The flue can be increased in size from the boiler take off point providing the joint is correctly sealed. Never reduce the flue diameter from the boiler take off point.
- The flue should be vertical and contain as few bends as possible, a maximum of two 135° bends should be used
- The flue outlet must be extended beyond the eaves of the building and where possible, above the apex
- Fit a suitable anti down-draught terminal where down draughts are experienced
Send enquiry
Send us an enquiry via our website and we'll get back to you as soon as we can.
Register guarantee
Register your Worcester Bosch product here by following a few simple steps.
Manuals & brochures
Lost the instructions? Don't worry. Download PDF copies of product user manuals, instructions or brochures here.
Customer support
Find out about our service plans and book your next appointment.
Customer relations
Please contact our customer relations team if you have any feedback, comments or criticism of our products or services.